Image Map
029 2046 3345

ELEKTROGAS VMR GAS SOLENOID VALVES - AUTO RESET

The VMR type valve is a fast opening single-stage solenoid valve, normally closed (open when energized). This type of device is suitable for air or gas blocking and releasing controls, In gas power burners, atmospheric gas boilers, industrial kilns and others gas consuming appliances.

Maximum pressure 200MBAR

                  Certificate

                  Certificate

        Power Consumption

Features

  • The valves are made of aluminum alloy die-cast (or hotpressed brass for OTN versions), with a wide range for inlet/outlet connections from DN 8 up to DN 150.
  • Suitable for use with air and non-aggressive gases included in the 1, 2 and 3 families (EN 437) and Pipe connections meet group 2 and back pressure sealing is compliant to Class A EN161 approval.
  • This valve is open only when energized: if, for any reason, power supply goes down, the valve closes immediately (intrinsic safe).
  • Qualified for continuous service (100% ED).
  • An incorporated fine mesh fitter protects the valve seat and disc as well as downstream components and prevents dirty contamination (except brass models). • Provided with G1/4 pressure tappings on two sides in the inlet chamber (except brass models).
  • Flanged models are provided with tappings in the outlet chamber too. Other tapping points on request.
  • Provided with G1/8 connection on the bottom for closed position indicator micro switch from
  • DN65 to DN150 (on request from 3/4" to 2").
PART NUMBERSIZE CONNECTION TYPE
VMR121/2" SCREWED
VMR223/4" SCREWED
VMR321" SCREWED
VMR3521 1/4" SCREWED
VMR421 1/2" SCREWED
VMR622" SCREWED
VMR722 1/2" FLANGED
VMR823" FLANGED
*VMR924" FLANGED
*VMR9325" FLANGED
*VMR9526" FLANGED

SPARE COILS AVAILABLE ON REQUEST
PRICE ADDITIONS: +10% 24V, +10% IP65
+£5.00 (PER VALVE) 4 TEST POINT (UP TO 2”)
STANDARD ON LARGER FL. VALVES
*NOTE: FOR 4”, 5” & 6” FLANGED VALVES, AFTER DE-ENERGISING
THE VALVES, YOU MUST WAIT AT LEAST 5 SECONDS BEFORE
SWITCHING IT BACK ON AGAIN. THIS IS TO ALLOW THE CAPACITOR
ENOUGH TIME TO RE-CHARGE.

Heat & Combustion Supplies

Unit E5, Southpoint Industrial Estate
Foreshore Road, Cardiff Bay, Cardiff CF10 4SP

Tel: +44 (0) 29 20 463345
Fax: +44 (0) 29 20 463346

sales@heatcombustion.co.uk
www.heatcombustion.co.uk

Disclaimer:
Please refer to manufacturers documentation for
full safety specification and correct fitting.